Sensorlink Fiber optic coupled voltmeter, 40kV – 8-014
40 kV Volt LiteWire, fiber optic linked sensor, analog output & 7-047 Insulated Electrode
Range of Operation
Voltage 40 KV Volt Litewire: 1 – 40 kVAC
Frequency: 60Hz (57 to 63) or 50 Hz (47 to 53 Hz) Models available
Accuracy
Volts: ± 2%
Resolution 30KV Volt Litewire
Voltage: 1 – 20 kVAC: 10V
Voltage: 20 – 40 kVAC: 100V
Analog Output
40KV Volt Litewire: 50 MV per kV (2 volts = 40 kV)
Output impedance
6000 ohms, minimum
Frequency Response
2500 Hz which is above the 40th harmonic at 50 or 60 Hz
Fiber Optic Cable
Length: 40’, 12.19 m
Isolation: 100 kV per foot, 500 kV max
Mechanical
Electrodes: Detachable
40KV Volt Litewire Weight: 5.5 lbs, 2.50 kg
Housing: Shock & water resistant molded urethane
Hot stick Mounting: Universal chuck adapter (hot stick not included)
Battery: Two each 9V alkaline or lithium; one each in Sensor and Receiver
Battery Life: Minimum 4 hours of continuous use
Operating temperature: -22° to +140° F, -30° to +60° C
Lithium battery required for use below -4°F, -20° C
Display: None; unit must be connected to a power quality analyzer